Nomenclature - Omron CQM1 Operation Manual

Sysmac cqm1h/cqm1 series dedicated i/o units
Hide thumbs Also See for CQM1:
Table of Contents

Advertisement

Nomenclature

2-1
Nomenclature
CQM1-G7M21 Master
Front View
Transmission Ready terminals
(Refer to 3-2 External Output
Connection Cables)
Terminals shorted while in trans-
mission status with power on.
Read signal at CPU and confirm
transmission ready status be-
fore enabling data.
Refer to 4-2 Handling Power On.
The output from these ter-
minals linked to ON/OFF status
of the T/R RDY indicator.
ALM output terminals
(Refer to 3-2 External Output
Connection Cables)
Terminals shorted if an error oc-
curs in the output of a unit with
error detection function
(G730-ROC04-A).
Indicators
36
Terminal screws: M3
(Optimum tightening torque: 0.5 N m)
Name
RDY
Unit Ready
IN 1CH
IN Mode
OUT 1CH
OUT Mode
T/R RDY
Transmission
Ready
HOLD
HOLD Setting
T/R
Transmitting
END
Terminator
Indicators (see following table)
+
Transmission terminal
(Refer to 3-1 Transmission Cables)
For connection of transmission
cable to Expansion Master or
Slave.
Color
Green
Lit when power is on and if CQM1H/
CQM1 recognizes a Master.
Orange
Lit while number of inputs set to 1 word
(16 points). Not lit when set to 2 words
(32 points).
Orange
Lit while number of outputs set to 1
word (16 points). Not lit when set to 2
words (32 points).
Green
Lit while in transmission status with
power on. Not lit while in transmission
error.
Orange
Lit while DIP switch set to HOLD (data
held when a transmission error occurs).
Red
Flashes while searching for terminator
or during transmission with power
turned on. Lit when there is a transmis-
sion error. Not lit when there is an error
in the Master.
Red
Lit when the power is turned on. Goes
out when the terminator is found.
Flashes when multiple terminators are
present.
Section 2-1