Omron CQM1 Operation Manual page 174

Sysmac cqm1h/cqm1 series dedicated i/o units
Hide thumbs Also See for CQM1:
Table of Contents

Advertisement

Operation without CQM1-TU001 Remote Console
Light Axis Adjustment
with Flashing Function
4. Move the object and press the teaching button. If teaching is successful,
the teaching indicator will turn from orange to green. If teaching is unsuc-
cessful, the teaching indicator (orange) will flash, in which case change the
position of the object and the sensing distance that have been set and re-
peat from step 3.
Light is received.
5. Set the mode selector to RUN to complete the sensitivity setting on the
E3X-MA11.
• This function enables the user to easily adjust the light axis of a thru-
beam fiber with the light source flashing.
• If the light projection fiber head axis and the light reception fiber head axis
do not agree with each other, and the amount of light received becomes
90% of the peak value or less, the flashing function of the E3X-MA11 will
operate. The E3X-MA11 retains the peak value when the mode selector is
set to SET so that the axes of the fiber heads can be easily adjusted to
agree with each other. When the axes agree, the tip of the fiber for light
emission will be lit.
• If a Remote Console is connected to the Sensor Unit, the buzzer of the
Remote Console will beep intermittently when the flashing function starts
operating. The buzzer will stop beeping when the axes agree and the tip
of the fiber for light emission is lit.
• Teaching is possible by pressing the teaching button while the flashing
function is operating.
Fiber for light emission
Mark
Base
Optical
input
The peak of
light reception
90% of the
peak value
Flashing
Lit
Flashing
Section 4-1
Fiber for light
reception
Lit in
this
range.
Angle of
the head
( )
155