2-1-2 Switch Settings

Unit Number Switch

2-1-3 Wiring

Compatible Connector
The unit number (MACHINE No.) is the only setting necessary on the Analog
Input Unit. Always turn off the power before setting the unit number. Use a flat-
blade screwdriver, being careful not to damage the slot in the screw. Be sure not
to leave the switch midway between settings.
Switch setting
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Note
1. The unit number setting switch is factory set to 0.
2. If two or more Special I/O Units are assigned the same unit number, an I/O
UNIT OVER error will be generated and the PC will not operate.
3. Make the unit number settings with the power turned off to the PC. If the set-
tings are made with the power on, they will not go into effect until either the
power is turned off and then on again or the Special I/O Unit Restart Flag
(AR0100 to AR0109) is turned ON and then OFF again.
4. The unit number can be set to between A and F Hex (10 to 15 decimal) only
when a C200H-AD002 with a lot number jj16 or later (January 1996 or
later) is used with a C200HG-CPU53/CPU63 or C200HX-CPU54/CPU64
CPU Unit.
One MR-34LFG Connector Set is included with each Unit. The set includes an
MR-34FG Connector and MR-34L Cover made by Honda Communications.
Unit number
IR words
Unit #0
IR 100 to 109
Unit #1
IR 110 to 119
Unit #2
IR 120 to 129
Unit #3
IR 130 to 139
Unit #4
IR 140 to 149
Unit #5
IR 150 to 159
Unit #6
IR 160 to 169
Unit #7
IR 170 to 179
Unit #8
IR 180 to 189
Unit #9
IR 190 to 199
Unit #10
IR 400 to 409
Unit #11
IR 410 to 419
Unit #12
IR 420 to 429
Unit #13
IR 430 to 439
Unit #14
IR 440 to 449
Unit #15
IR 450 to 459
Section 2-1
DM words
DM 1000 to 1043
DM 1100 to 1143
DM 1200 to 1243
DM 1300 to 1343
DM 1400 to 1443
DM 1500 to 1543
DM 1600 to 1643
DM 1700 to 1743
DM 1800 to 1843
DM 1900 to 1943
DM 2000 to 2043
DM 2100 to 2143
DM 2200 to 2243
DM 2300 to 2343
DM 2400 to 2443
DM 2500 to 2543