teaching button is pressed. While teaching, the buzzer will beep once
when the teaching button is pressed. If teaching is not successful, the
buzzer will beep three more times.
2. Teaching operations on the CQM1-TU001 precede operations on sensor
modules.
Name
Color
OPERATION
Orange
STABILITY
Green
TEACHING
Red/Green
• The module selected is set to the operation monitor mode or teaching
mode using the mode setting selector of the CQM1-TU001.
• When the CQM1-TU001 is in operation monitor mode, the operation of
the module selected with the module selector of the CQM1-TU001 can be
monitored with the operation indicator and stability operation indicator of
the CQM1-TU001.
• When the module selector is set to the 0, module 0 will be selected. Slide
the module selector and set to 1 for module 1, 2 for module 2, and 3 for
module 3.
• Set the mode setting selector to SET before setting the Sensor Unit to the
teaching mode and set the mode setting selector to RUN before setting
the Sensor Unit to the operation monitor mode.
The READY indicator (green) is lit when the I/O bus of the CQM1-SEN01 is
ready to retrieve signals after the CQM1-SEN01's address is set properly with
the CPU. The output indicators (orange) are lit according to the operation of
each module inserted to slots 0 to 3 of the CQM1-SEN01.
• The stability operation indicator (green) and operation indicator (orange)
of the CQM1-TU001 correspond to the stability operation indicator (green)
and operation indicator (orange) of each sensor module.
• The teaching indicator (red/green) on the CQM1-TU001 is used as a
teaching monitor for the module selected.
• The operation indicator is lit when a sensing object is within the sensing
distance and the object will be detected. The stability operation indicator
shows the stability of detecting or non-detecting operations. The stability
operation indicator will be lit when a sensing object is located 0.93 times
as near as the sensing distance or less. The stability operation indicator
will be also lit when a sensing object is located 1.07 times as far as the
sensing distance or more.
Function
Lit when the control output of the sensor module
specified with the module selector is ON.
Lit when the operation of the sensor module speci-
fied with the module selector is stable.
Indicates the teaching status of sensitivity setting.
Section 2-1
139