Emc Standards For An Ah Motion System; Emc Standards Applicable To An Ah Motion System - Delta AH Motion Series Hardware Manual

Table of Contents

Advertisement

AH Mo t io n – H ar d war e M a nu a l
A.1 EMC Standards for an AH Motion System
A.1.1 EMC Standards Applicable to an AH Motion System
The EMC standards which are applicable to an AH Motion system are listed below.
 EMI
Port
Enclosure port
(radiated)
(measured at a distance
of 10 meters)
AC power port
(conducted)
 EMS
Environmental
phenomenon
Electrostatic discharge
_A
Radio frequency
electromagnetic field
Amplitude modulated
Power frequency magnetic
A - 2
Frequency range
30-230 MHz
230-1000 MHz
0.15-0.5 MHz
0.5-30 MHz
Reference
standard
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-8
field
Level (Normative)
40 dB (μV/m) quasi-peak
47 dB (μV/m) quasi-peak
79 dB (μV) quasi-peak
66 dB (μV) average
73 dB (μV) quasi-peak
60 dB (μV) average
Test
Contact
Air
2.0-2.7 GHz
80% AM,
1.4-2.0 GHz
1 kHz sinusoidal
80-1000 MHz
60 Hz
50 Hz
Reference standard
IEC 61000-6-4
IEC 61000-6-4
Test level
± 4 kV
± 8 kV
1 V/m
3 V/m
10 V/m
30 A/m
30 A/m