Emc Standards For An Ah Motion Controller System; Emc Standards Applicable To An Ah Motion Controller System - Delta AH Series Hardware Manual

Motion controller
Hide thumbs Also See for AH Series:
Table of Contents

Advertisement

AH Mo t io n C on tr o ll er – Har d war e M a nu a l
A.1 EMC Standards for an AH Motion Controller System
A.1.1 EMC Standards Applicable to an AH Motion Controller System
The EMC standards which are applicable to an AH Motion Controller system are listed below.
 EMI
Port
Enclosure port
(radiated)
(measured at a distance
of 10 meters)
AC power port
(conducted)
 EMS
Environmental
phenomenon
Electrostatic discharge
_A
Radio frequency
electromagnetic field
Amplitude modulated
Power frequency magnetic
A - 2
Frequency range
30-230 MHz
230-1000 MHz
0.15-0.5 MHz
0.5-30 MHz
Reference
standard
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-8
field
Level (Normative)
40 dB (μV/m) quasi-peak
47 dB (μV/m) quasi-peak
79 dB (μV) quasi-peak
66 dB (μV) average
73 dB (μV) quasi-peak
60 dB (μV) average
Test
Contact
Air
2.0-2.7 GHz
80% AM,
1.4-2.0 GHz
1 kHz sinusoidal
80-1000 MHz
60 Hz
50 Hz
Reference standard
IEC 61000-6-4
IEC 61000-6-4
Test level
± 4 kV
± 8 kV
1 V/m
3 V/m
10 V/m
30 A/m
30 A/m