C.1 EMC Standards for an AS Series System
C.1.1 DVP-ES3 Series System EMC Standards
The EMC standards that are applicable to a DVP-ES3 series system are listed in the following tables.
EMI
Enclosure port
(radiated)
(measured at a
distance of 10 meters)
AC power port
(conducted)
EMS
Environmental
phenomenon
Electrostatic
_C
discharge
Radio frequency
electromagnetic field
Amplitude modulated
Power frequency
magnetic field
C - 2
Port
Frequency range
30-230 MHz
230-1000 MHz
0.15-0.5 MHz
0.5-30 MHz
Reference
standard
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-8
Level (Normative)
40 dB (μV/m) quasi-peak
47 dB (μV/m) quasi-peak
79 dB (μV) quasi-peak
66 dB (μV) average
73 dB (μV) quasi-peak
60 dB (μV) average
Test
Contact
Air
2.0-2.7 GHz
1.4-2.0 GHz
80% AM,
1 kHz sinusoidal
2.0-2.7 GHz
2.7-6.0 GHz
60 Hz
50 Hz
Reference standard
IEC 61000-6-4
IEC 61000-6-4
Test level
± 4 kV
± 8 kV
1 V/m
3 V/m
3 V/m
3 V/m
30 A/m
30 A/m