Wiring Ah08Da-5B - Delta AH Motion Series Hardware Manual

Table of Contents

Advertisement

AH Mo t io n – H ar d war e M a nu a l
*1. Please use a shielded cable as an analog output cable, and isolate the shielded cable from other power cables.
*2. If the ripple voltage of the input terminal of the load connected is large, and results in interference with the wiring,
please connect a 0.1~0.47 μF and 25 V capacitor.
*3. Please connect the terminal SLD to the terminal SG. Once the module is installed on a backplane, the module's
terminal SG and the backplane's terminal
terminal
to the ground terminal
4.10.5

Wiring AH08DA-5B

AC motor drive,
recorder,
proportioning valv e. ..
AC motor drive,
recorder,
proportioning valv e. ..
_4
1. Please use a shielded cable as an analog output cable, and isolate the shielded cable from other power cables.
*2. If the ripple voltage of the input terminal of the load connected is large, and results in interference with the wiring,
please connect a 0.1~0.47 μF and 25 V capacitor.
*3. Please connect the ground in the shielded cable to the terminal SG.
*4. Once the module is installed on a backplane, the module's terminal SG and the backplane's terminal
short circuit. In this case, please connect the backplane's terminal
4 - 1 0 0
will be a short circuit. In this case, please connect the backplane's
.
Voltage output
-10V ~+10V
*2
Shielded cable*1
*3
SG
Voltage output
-10V ~+10V
*2
Shielded cable*1
*3
SG
24VDC
CH0
VO0
AG
AG
CH7
VO7
AG
AG
*4
SG
ZP
convert er
UP
to the ground terminal
CH0
CH7
+15V
DC/DC
AG
-15V
will be a
.