Wiring Temperature Measurement Modules; Wiring Ah04Pt-5A - Delta AH Motion Series Hardware Manual

Table of Contents

Advertisement

*1. Please use a shielded cable as an analog input cable, and isolate the shielded cable from other power cables.
*2. If current is connected, the connection between Vn+ and In+
*3. If ripple voltage results in interference with the wiring, please connect a 0.1~0.47 μF and 25 V capacitor.
*4. Please isolate the analog output cable from other power cables.
*5. If the ripple voltage of the input terminal of the load connected is large, and results in interference with the wiring,
please connect a 0.1~0.47 μF and 25 V capacitor.
*6. Please connect the ground wire in the shielded cable to the terminal SG.
*7. Once the module is installed on a backplane, the module's terminal SG and the backplane's terminal
short circuit. In this case, please connect the backplane's terminal

4.11 Wiring Temperature Measurement Modules

4.11.1

Wiring AH04PT-5A

Ω
0 ~3 00
Ni 10 0/Ni 10 00
P t10 0/P t10 00
2 -wi re
Ω
0 ~3 00
Ni 10 0/Ni 10 00
P t10 0/P t10 00
3 -wi re
Ni 10 0/Ni 10 00
P t10 0/P t10 00 *2
4 -wi re
*1. The cable connected to the input terminal should be the cable or the shielded twisted pair cable which can be
connected to an Ni100/Ni1000/Pt100/Pt1000 sensor, and should be kept separate from other power cables and
cables which generate noise. Please use a three-wire temperature sensor. If you want to use a two-wire temperature
sensor, On+ and In+ must be short-circuited, and On- and In- must be short-circuited. (n is in the range of 0 to 3.)
*2. If you want to measure resistance in the range of 0 Ω to 300 Ω, you can use a two-wire or three-wire sensor instead of
a four-wire sensor.
*3. You need to select an appropriate sensor. If an Ni100 temperature sensor, a Pt100 temperature sensor, or a
resistance sensor is used, the internal excitation current is 1.53 mA. If an Ni1000 temperature sensor, or a Pt1000
temperature sensor is used, the internal excitation current is 204.8 μA.
S hi el de d ca bl e*1
CH0
S hi el de d ca bl e*1
CH1
S hi el de d ca bl e*1
CH3
Ch a pt er 4 Ins t al l at i o n an d W ir in g
needs to be a short circuit.
(n=0~7)
to the ground terminal
O 0+
I0 +
I0-
O0 -
AG
FG
O 1+
I1 +
I1-
O1 -
AG
FG
O 3+
I3 +
I3-
O3 -
FG
AG
will be a
.
1 .53 mA (Ni 10 0
se nso r Pt1 00
,
se nso r, or
r esi stor )/2 04 .8u A
( Pt1 00 0) *3
ADC
INA
4 - 1 0 3
4_

Advertisement

Table of Contents
loading

Table of Contents