Wiring Ah08Ad-5B - Delta AH Motion Series Hardware Manual

Table of Contents

Advertisement

AH Mo t io n – H ar d war e M a nu a l
*1. Please use a shielded cable as an analog input cable, and isolate the shielded cable from other power cables.
*2. If current is connected, the connection between Vn+ and In+ needs to be a short circuit. (n= 0 ~7.)
*3. If ripple voltage results in interference with the wiring, please connect a 0.1~0.47 μF and 25 V capacitor.
*4. Please connect the ground in the shielded cable to the terminal SG.
*5. Once the module is installed on a backplane, the module's terminal SG and the backplane's terminal
short circuit. In this case, please connect the backplane's terminal
4.10.2

Wiring AH08AD-5B

4- wir e co nn ecti on :
vol tag e i np ut
-10V~+10V
+24V
0V
Po siti on tra nsd uce r o r
pr op or tio ni ng val ve
3- wir e co nn ecti on :
vol tag e i np ut
-10V~+10V
+24V
_4
0V
Po siti on tra nsd uce r o r
pr op or tio ni ng val ve
*1. Please use a shielded cable as an analog input cable, and isolate the shielded cable from other power cables.
*2. If ripple voltage results in interference with the wiring, please connect a 0.1~0.47 μF and 25 V capacitor.
*3. Please connect the terminal SLD to the ground terminal
4 - 9 8
Sh ie ld ed cab le
+
-
Sh ie ld ed cab le
+
-
to the ground terminal
*1
CH0
V0+
* 2
V0-
SLD
*1
CH7
V7+
V7-
SLD
* 3
.
.
AG
1M
CH0
1M
AG
1M
CH7
1M
will be a