Programmable Safety Controller SCR P
EtherNet/IP Assembly Objects
Note: The EDS file is available for download at
Industrial Ethernet Overview
Input (T->O) Assembly Objects
Instance ID
Data Length (16-bit words)
100 (0×64)
101 (0×65)
102 (0×66)
103 (0×67)
104 (0×68)
Output (O->T) Assembly Object
Instance ID
Data Length (16-bit words)
112 (0×70)
113 (0×71)
114 (0×72)
Configuration Assembly Object
The Configuration Assembly Object is not implemented. However, some EtherNet/IP clients require one. If this is
the case, use Instance ID 128 (0×80) with a data length of 0.
Set the Data Type of the communication format to INT.
Set the RPI (requested packet interval) to a minimum of 150.
96
www.bernstein.eu.
on p. 109.
Description
8
Used to access the basic information about the Virtual Status Outputs 1–64.
Used to access the advanced information (including the basic information)
104
about the Virtual Status Outputs.
Used to access the fault log information and provides no Virtual Status
150
Output information.
Used to access the basic information about Virtual Status Outputs 1–256
35
and feedback information about Virtual Reset and Virtual Cancel Delay
inputs. Available on SCR P.
Used to access the basic information about Virtual Status Outputs 1–256,
112
feedback information about Virtual Reset and Virtual Cancel Delay inputs,
and to support communications with DCD-enabled devices.
Description
2
Reserved
11
Used to control Virtual Inputs (On/Off, Mute Enable, Reset, Cancel Delay).
Available on SCR P.
14
Used to control Virtual Inputs (On/Off, Mute Enable, Reset, Cancel Delay)
and to support communications with DCD-enabled devices.