12 Troubleshooting

The Safety Controller is designed and tested to be highly resistant to a wide variety of electrical noise sources that are
found in industrial settings. However, intense electrical noise sources that produce EMI or RFI beyond these limits may
cause a random trip or lockout condition. If random trips or lockouts occur, check that:
The supply voltage is within 24 V dc ± 20%
The Safety Controller's plug-on terminal blocks are fully inserted
Wire connections to each individual terminal are secure
No high-voltage or high-frequency noise sources or any high-voltage power lines are routed near the Safety
Controller or alongside wires that are connected to the Safety Controller
Proper transient suppression is applied across the output loads
The temperature surrounding the Safety Controller is within the rated ambient temperature (see
Requirements
on p. 12)

12.1 Software: Troubleshooting

Live Mode button is unavailable (grayed out)
1. Make sure the USB cable is plugged into both the computer and the Safety Controller.
Note: Make sure you use USB cables that the cable includes a communication line. Many cell
phone charging cables do not have a communication line.
2. Verify that the Safety controller is installed properly—see
3. Exit the Software.
4. Unplug the Safety controller and plug it back in.
5. Start the Software.
Unable to read from the Safety Controller or send the configuration to the Safety Controller (buttons grayed out)
1. Make sure Live Mode is disabled
2. Make sure the USB cable is plugged into both the computer and the Safety Controller
Note: Make sure you use USB cables that the cable includes a communication line. Many cell
phone charging cables do not have a communication line.
3. Verify that the Safety Controller is installed properly—see
4. Exit the Software.
5. Unplug the Safety Controller and plug it back in.
6. Start the Software.
Unable to move a block to a different location
Not all blocks can be moved. Some blocks can be moved only within certain areas.
Safety Outputs are placed statically and cannot be moved. Referenced Safety Outputs can be moved
anywhere within the left and middle areas.
Safety and Non-Safety Inputs can be moved anywhere within the left and middle areas.
Function and Logic blocks can be moved anywhere within the middle area.
SC-XM2/3 button is unavailable (grayed out)
1. Make sure all connections are secure—SCR P-PA to the USB port of the computer and to the SCR P-FPS drive.
2. Verify that the SCR P-PA Programming Tool is installed properly—see
3. Exit the Software.
4. Disconnect and re-connect all connections— SCR P-PA to the USB port of the computer and to the SCR P-FPS
drive.
5. Start the Software.
184
Verifying Driver Installation
Verifying Driver Installation
www.bernstein.eu
- Tel: + 49 571 793 0
Specifications and
on p. 186.
on p. 186.
Verifying Driver Installation
on p. 186.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scr p-10-6r-46075133159

Table of Contents