Banner SCR P Series Instruction Manual page 117

Safety controller
Table of Contents

Advertisement

WORD #
WORD NAME
77–84
Fault #6 Name of I/O or System
85
Fault #6 Error Code
86
Fault #6 Advanced Error Code
87
Fault #6 Error Message Index
reserved
88–89
90–91
Fault #7 Time Stamp
92–99
Fault #7 Name of I/O or System
100
Fault #7 Error Code
101
Fault #7 Advanced Error Code
102
Fault #7 Error Message Index
103–104
reserved
105–106
Fault #8 Time Stamp
107–114
Fault #8 Name of I/O or System
115
Fault #8 Error Code
116
Fault #8 Advanced Error Code
117
Fault #8 Error Message Index
reserved
118–119
120–121
Fault #9 Time Stamp
122–129
Fault #9 Name of I/O or System
130
Fault #9 Error Code
131
Fault #9 Advanced Error Code
132
Fault #9 Error Message Index
133–134
reserved
135–136
Fault #10 Time Stamp
137–144
Fault #10 Name of I/O or System
145
Fault #10 Error Code
146
Fault #10 Advanced Error Code
147
Fault #10 Error Message Index
reserved
148–149
Fault Time Stamp
The relative time, in seconds, when the fault occurred. As measured from time 0, which is the last time the Safety
Controller was powered up.
Name of I/O or System
This is an ASCII-string describing the source of the fault.
Error Code, Advanced Error Code, Error Index Message
The Error Code and the Advanced Error Code, taken together, form the Safety Controller Fault Code. The format for
the Fault Code is Error Code 'dot' Advanced Error Code. For example, a Safety Controller Fault Code of
2.1 is represented by an Error Code of 2 and an Advanced Error Code of 1. The Error Message Index value is the
Error Code and the Advanced Error Code together, and includes a leading zero with the Advanced Error Code, if
necessary. For example, a Safety Controller Fault Code of 2.1 is represented by an Error Message Index of 201.
The Error Message Index value is a convenient way to get the complete Fault Code while only reading a single 16-
bit register.
www.bernstein.eu
- Tel: + 49 571 793 0
Programmable Safety Controller SCR P
DATA TYPE
2-word length + 12-ASCII characters
16-bit integer
16-bit integer
16-bit integer
16-bit integer
32-bit integer
2-word length + 12-ASCII characters
16-bit integer
16-bit integer
16-bit integer
16-bit integer
32-bit integer
2-word length + 12-ASCII characters
16-bit integer
16-bit integer
16-bit integer
16-bit integer
32-bit integer
2-word length + 12-ASCII characters
16-bit integer
16-bit integer
16-bit integer
16-bit integer
32-bit integer
2-word length + 12-ASCII characters
16-bit integer
16-bit integer
16-bit integer
16-bit integer
117

Advertisement

Table of Contents
loading

This manual is also suitable for:

Scr p-10-6r-46075133159

Table of Contents