Internal Temperature = ((A–L) / (H–L)) × 5 + T
A
the ADC Value obtained from the controller
L
the ADC value on the lookup table less than or equal to A
H
the ADC value on the lookup table greater than A
T
the temperature associated with the L value
9.7.3 Actuator Distance
Convert the binary reading into a number. If the number matches an ADC value in the following table, read the distance. If
the number is between the readings in the table, use the following formula to obtain the actual distance.
www.bernstein.eu
- Tel: + 49 571 793 0
Programmable Safety Controller SCR P
Table 58: Temperature
ADC Reading
41
54
69
88
110
136
165
199
237
278
321
367
414
461
508
554
598
640
679
715
748
778
804
829
850
869
886
901
914
926
936
Temperature (°C)
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
163