Fault Code
Fault Code Description
2.2
Simultaneity Fault
2.3 or 2.5
Concurrency Fault
2.4 or 2.6
Simultaneity Fault
2.7
Internal Fault
2.8 – 2.9
Input Fault
2.10
Input Fault
2.11 – 2.12
Input Fault
2.13
Input Fault
2.14
Input Fault
2.15
Open Lead
2.16 – 2.18
Input Fault
2.19
Open Lead
2.20
Input Fault
2.21
Open Lead
2.22 – 2.23
Input Fault
Input Activated While
2.24
Bypassed
2.25
Input Fault
2.26
Input Fault
3.1
EDMxx Fault
On a dual-channel input, or a complementary input, one input went into the Run state but the
other input did not follow the change within 3 seconds.
On a dual-complementary input, one pair of inputs went into the Run state but the other pair of
inputs did not follow the change within 3 seconds.
Check the wiring
Check the input signal timing
Cycle input
On a dual-complementary input, with both inputs of one complementary pair in the Run state,
one input of this complementary pair changed to Stop then back to Run.:
Check the wiring
Check the input signals
Check the power supply providing input signals
Consider adjusting the debounce times
Cycle input
On a dual-complementary input, one input of a complementary pair went into the Run state, but
the other input of the same complementary pair did not follow the change within the time limit:
Check the wiring
Check the input signal timing
Cycle input
Internal failure— Contact BERNSTEIN AG (see
Input stuck high:
Check for shorts to other inputs or other voltage sources
Check the input device compatibility
Check for a short between inputs
Check for a short to ground
Input stuck low
Check for a short to ground
Missing test pulses:
Check for a short to other inputs or other voltage sources
Check for an open lead
Missing test pulses:
Check for a short to other inputs or other voltage sources
Check for an open lead
Missing test pulses:
Check for a short to ground
Check for an open lead
Check for an unstable signal on the input
A Two-Hand Control input was activated (turned On) while it was bypassed.
After the associated Safety Output turned Off, the AVM input did not close before its AVM
monitoring time expired:
The AVM may be disconnected. Check the wiring to the AVM
Either the AVM is disconnected, or its response to the Safety Output turning Off is
too slow
Check the wiring to the AVM
Check the timing setting; increase the setting if necessary
Contact BERNSTEIN
The AVM input was open, but should have been closed, when the associated Safety Output was
commanded On:
The AVM may be disconnected. Check the wiring to the AVM
EDM contact opened prior to turning On the Safety Outputs:
Check for a stuck On contactor or relay
Check for an open wire
www.bernstein.eu
- Tel: + 49 571 793 0
Programmable Safety Controller SCR P
Steps to resolve
Repairs and Warranty Service
on p. 191)