Frequency Selector - Siemens SICAM Manual

Earth fault indicator
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

By default, the ground-fault BO type is Latch.
NOTE
i
i
In 6MD2311-1BB00-0AA3 and 6MD2311-1BE00-0AB6 MLFB variants, the spare BO (terminal X6) can be
used as either ground fault BO or signal lamp output. If used as a ground fault BO, the BO type can be
Wipe/Latch type. If the X6 terminal is used as signal lamp output, the BO type is Latch.
Frequency Selector
5.4.10
The frequency selector feature enables you to select the system frequency of the electrical network in which
the device is mounted. Based on the position of DIP 9 in DIP Switch (S4), the frequency can be selected as
follows:
DIP 9
OFF
ON
By default, the frequency selected is 50 Hz except in 6MD2311-1DC10-0AB6 MLFB variant, wherein the
default frequency selected is 60 Hz.
.
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022
Frequency
50 Hz
60 Hz
Device Functions
5.4 DIP Switch
69

Advertisement

Table of Contents
loading