Introduction
F US Clamp-on
Communications Module Kit
F US Clamp-on
Communications Module
Installation
BACnet Communications
BACnet Protocol
Implementation
Conformance Statement
1
2
3
4
5

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS F US

  • Page 1 Introduction F US Clamp-on Communications Module Kit F US Clamp-on Communications Module Installation SITRANS F BACnet Communications Ultrasonic Flowmeters SITRANS F US Clamp-on BACnet Protocol Implementation Communications Module Conformance Statement Hardware Installation Instructions 2/2014 A5E32586525-AD...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Profile Selection: 1 - 46 ........................ 16 Figures Figure 3-1 New Communications Module Installation ................... 11 Figure 3-2 SITRANS F US Clamp-on Communications Module A5E31949269 ........... 12 Figure 3-3 New Communications Module Installation ................... 13 Figure 3-4 SITRANS F US Clamp-on Communications Module A5E31949269 ........... 14 Figure 3-5 DIP Switches SW1-A and SW2-B ....................
  • Page 4 Table of contents SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 5: Introduction

    Introduction These SITRANS F US Clamp-on Communications Module installation instructions are for Siemens SITRANS F US clamp-on ultrasonic flow meters. The instructions are aimed at persons that mechanically install the device, connect it electronically, configure the parameters and commission it as well as service and maintenance engineers.
  • Page 6 Introduction SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 7: F Us Clamp-On Communications Module Kit

    F US Clamp-on Communications Module Kit The following parts are supplied: ● SITRANS F US Clamp-on Communications Module A5E31949269 Revision AA ● Four captive screws ● Four captive standoffs ● 6-position connector SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 8 F US Clamp-on Communications Module Kit SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 9: F Us Clamp-On Communications Module Installation

    3. Fielded flow meters with existing Communications Module. Required installation procedures include: ● Removal of the existing communications module ● Installation of Communications Module (no mounting kit necessary) SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 10 2. Open the flow meter cover by releasing the side cover latch ② 3. Loosen the I/O Module cover captive screw and remove the cover, screw and standoff. SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 11: Figure 3-1 New Communications Module Installation

    5. Install the new standoffs supplied in the mounting kit in the vacant positions. 6. Place the Communications Module over the I/O Module and align connector J3 with P1 of the I/O Module (figure 3-2). SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 12: Figure 3-2 Sitrans F Us Clamp-On Communications Module A5E31949269

    Standoff ④ Figure 3-2 SITRANS F US Clamp-on Communications Module A5E31949269 7. Gently press the Communications Module down to connect it to the I/O Module. 8. Tighten the captive screws to secure the Communications Module and I/O Module. 9. If using Ethernet IP, connect the Ethernet connector.
  • Page 13: Figure 3-3 New Communications Module Installation

    6. Install the new standoffs supplied in the mounting kit in the vacant positions. 7. Place the Communications Module over the I/O Module and align connector J3 with P1 of the I/O Module (figure 3-4). SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 14: Figure 3-4 Sitrans F Us Clamp-On Communications Module A5E31949269

    Standoff ④ Figure 3-4 SITRANS F US Clamp-on Communications Module A5E31949269 8. Gently press the Communications Module down to connect it to the I/O Module. 9. Tighten the captive screws to secure the Communications Module and the I/O Module. 10.If using Ethernet IP, connect the Ethernet connector.
  • Page 15: Figure 3-5 Dip Switches Sw1-A And Sw2-B

    19200 A7 ON A8 OFF 38400 A7 OFF A8 ON 76800 A7 ON A8 ON Profile Selection: B1-B6 See selection table 3-1. Protocol Selection: B7-B8 BACnet IP/BACnet MSTP B7 ON B8 OFF19200 SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 16: Table 3- 1 Profile Selection: 1 - 46

    Off On profile 21 5MN02-5.04.05 CH5: Clamp-On Off On profile 22 5MN02-5.04.05 QP: Clamp-On On On profile 23 5EN02-5.04.05 Ch1: Clamp-On On On profile 24 5EN02-5.04.05 Ch1: Reflexor SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 17 On Off profile 43 5GN03-5.04.05 CH1: Clamp-On On Off profile 44 5GN04-5.04.05 DP: Clamp-On Off On profile 45 5GN05-5.04.05 DP: Clamp-On Off On profile 46 5GN07-5.04.05 QP: Clamp-On SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 18 F US Clamp-on Communications Module Installation SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 19: Bacnet Communications

    BACnet Communications Introduction The Siemens SITRANS F US Clamp-on Flow Meters can be furnished with the Part Number A5E31949269 optional communications module card that provides BACnet communications over Ethernet or MSTP RS485. uilding utomation and ontrol works BACnet is a standard communication protocol for B developed by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
  • Page 20 Object_List {defined by profile selection} Max_APDU_Length_Accepted 1458 Segmentation_Supported 3 – no segmentation Local_Time 10:36:13 Local_Date 1/21/2013 APDU_Timeout 10000 Number_Of_ADPU_Retries Device_Address_Binding Database_Revision Active COV Subscriptions UTC Offset Description Location SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 21 3 – Binary Input Present_Value Description Character String (e.g. C1_Pipe_Empty) Status_Flags IN_ALARM,FAULT,OVERRIDDEN,OUT_OF_SERVICE (e.g 0000) Event_State 0 - Normal Out_Of_Service 0 - False Reliability Active Text Active Inactive Text Inactive SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 22 BACnet Communications SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 23: Bacnet Protocol Implementation Conformance Statement

    ☑ K.5.4 BIBB – Device Management – Dynamic Object Binding – B (DM-DOB-B) ☑ K.5.6 BIBB – Device Management – Device Communication Control – B (DM-DCC-B) ☑ K.5.12 BIBB – Device Management – Time Syncronization – B (DM-TS-B) SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 24 ⃞ BACnet IP, (Annex J), Foreign Device ⃞ ISO 8802-3, Ethernet (Clause 7) ⃞ ATA 878.1, 2.5 Mb. ARCNET (Clause 8) ⃞ ATA 878.1, EIA-485 ARCNET (Clause 8), baud rate(s) SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 25 ⃞ ISO 10646 (UCS-2) ⃞ ISO 10646 (UCS-4) ⃞ JIS X 0208 ☑ ANSI X3.4 If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports: Siemens F US Clamp-On Flow Meters. SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...
  • Page 26 BACnet Protocol Implementation Conformance Statement SITRANS F US Clamp-on Communications Module Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD...