Auto Reclosure Time Setting; Ground-Current Inrush; Bo Type Configuration (For Ground Fault) - Siemens SICAM Manual

Earth fault indicator
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Device Functions
5.4 DIP Switch
Battery-Powered Variants: Fault Auto-Reset Time Settings
Table 5-5
DIP 3
OFF
OFF
ON
ON
Dual-Powered Variants: Fault Auto-Reset Time Settings
Table 5-6
DIP 3
OFF
OFF
ON
ON
5.4.7
Auto Reclosure Time Setting
The auto reclosure time feature is enabled in the device based on the position of DIP 5 in DIP Switch (S4). The
following table displays the DIP switch position for enabling the feature.
DIP 5
OFF
ON
By default, the auto reclosure time setting is Disable.
Ground-current Inrush
5.4.8
The ground-current inrush feature is enabled in the device based on the position of DIP 6 and DIP 7 in DIP
Switch (S4). The following table displays the DIP switch position for enabling the feature and the associated
time values.
DIP 6
OFF
OFF
ON
ON
By default, the inrush-current detection setting is Disable.
BO Type Configuration (for Ground Fault)
5.4.9
This feature enables you to configure the ground-fault BO type in the device. Based on the position of DIP 8 in
DIP Switch (S4), the ground-fault BO type can be configured as follows:
DIP 8
OFF
ON
68
Fault Auto-Reset Time Setting for Battery-Powered Variants
DIP 4
6MD2311-1BB00-0AA3
OFF
1 h (default)
ON
2 h
OFF
4 h
ON
8 h
Fault Auto-Reset Setting for Dual-Powered Variants
DIP 4
6MD2311-1DC00-0
AB6
OFF
4 h (default)
ON
8 h
OFF
16 h
ON
32 h
DIP 7
OFF
ON
OFF
ON
6MD2311-1BE00-0AB6
1 h (default)
2 h
4 h
8 h
6MD2311-1DC10-0
6MD2311-1DD00-
AB6
0AB6
4 h (default)
4 h (default)
8 h
8 h
10 h
16 h
16 h
32 h
Auto Reclosure Time
Disable
3 min
BO Type
Latch
Wipe
6MD2311-2BB10-0AA5
1 h (default)
2 h
4 h
8 h
6MD2311-1DE00-
0AB6
4 h (default)
8 h
16 h
32 h
Inrush-Current Detection Time
Disable
300 ms
1 s
Unused
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022