Siemens SICAM Manual page 60

Earth fault indicator
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Product Specifications
4.2 Type Testing
Electrical Test (for SICAM EFI with signal lamp and sensor)
Test
Short-circuit current withstand test IEC 62689-1
Rated dynamic current
Temperature rise
Mechanical Tests (for SICAM EFI with signal lamp and sensor)
Test
Vibration response test, Class 1
Mechanical Impact
Seismic test
Service Conditions (for SICAM EFI with signal lamp and sensor)
Test
Service Conditions
60
Reference Standard
IEC 62689-1
IEC 62689-1
Reference Standard
IEC 60068-2-6
IEC 62689-1
IEC 62262:2002
IEC 62689-1:2016
IEC 60068-3-3
Reference Standard
IEC 60721-3-4
Test Requirement
25 kA @ 3 s
12.5 kA @ 1 s
31.25 kA peak for 1 s
62.5 kA peak for 3 s
for sensors only
Class B, up to 105 °C
Test Requirement
Sinusoidal
Frequency: 10 Hz to 500 Hz
10 m/s2 amplitude 0.075 mm,
23 min.
Sweep rate: 1 oct./min
Number of sweep cycles: 2 cycles/
axis
Number of axes: 3 (X, Y, and Z)
Performance Criterion: B
IK07, Impact energy: 2 J
Frequency: 1 Hz to 8 Hz (hori-
zontal), ± 7.5 mm amplitude
Frequency: 1 Hz to 8 Hz (vertical),
± 3.5 mm amplitude
Frequency: 8 Hz to 35 Hz (hori-
zontal), 2 g acceleration
Frequency: 8 Hz to 35 Hz (vertical),
1 g acceleration
Sweep rate: 1 oct./min
Number of sweeps: 1/axes (3 direc-
tions)
Test Requirement
Applicable Classification: 4K25,
4K26, 4Z2, 4Z13, 4Z10, 4Z16, 4B3,
4S13, 4M11
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022