Earth fault indicator
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Test
Exposure to solar radiation
Rainfall test
Storage temperature and transpor-
tation temperature
Insulation Test (for SICAM EFI)
Test
Dielectric test (50 Hz/60 Hz)
Impulse voltage test
1.2 μs/50 μs
Insulation resistance
Safety Test (for SICAM EFI)
Test
Product safety test
Ingress Protection (for SICAM EFI with signal lamp and sensor)
Test
Degree of protection
For optimum battery capacity, Siemens recommends storing the device below 30° C; 30 % RH.
19
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022
Reference Standard
IEC 60068-2-5
IEC 62689-1
-
IEC 60068-2-2
19
IEC 60068-2-1
IEC 62689-1
Reference Standard
IEC 61010-1
IEC 60255-27
IEC 61010-1
IEC 60255-27
IEC 61010-1
IEC 60255-27
Reference Standard
IEC 61010-1
Reference Standard
IEC 60529
Product Specifications
Test Requirement
1000 W/m
2
, Duration: 8 h
330 mm
-20° C to +75° C
Test Requirement
2.2 kV for 1 min
1.5 kV for 1 min
between X6 and X7 terminal
for 6MD2311-1BB00-0AA3 and
6MD2311-1BE00-0AB6 MLFB.
4 kV, 5 positive cycles, 5 negative
cycles
DC 500 V, 60 s, ≥100 MΩ
Test Requirement
Marking and Documentation as per Clause
No. 5
Protection Against Electric Shock as per
Clause No. 6
Protection against mechanical hazard as
per Clause No. 7
Resistance to mechanical stresses as per
Clause No. 8
Protection Against Spread of Fire as per
Clause No. 9
Equipment Temperature Limits and Resis-
tance to heat as per Clause No. 10
Protection against liberated gases and
substances, explosion, and implosion as
per Clause No. 13
Components and subassemblies as per
Clause No. 14
HAZARDS resulting from application as
per Clause No. 16
Risk Assessment as per Clause No. 17
Test Requirement
IP 65W (for EFI and signal Lamp)
IK07 (for EFI and signal Lamp)
IP 68W (for sensor)
4.2 Type Testing
59