Siemens SICAM Manual page 58

Earth fault indicator
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Product Specifications
4.2 Type Testing
Test
Power frequency magnetic field
immunity
Pulse magnetic field immunity
Damped oscillatory magnetic field
immunity
Radiated, radio frequency, electro-
magnetic field immunity
Conducted disturbances, induced
by radio frequency fields
Power frequency conducted distur-
bances
EMI/EMC Tests for Emission (for SICAM EFI with signal lamp)
Test
Conducted emission
Radiated emissions
Climatic Test (for SICAM EFI with signal lamp and sensor)
Test
Dry heat
Damp heat, steady state
Damp heat, cyclic (12 h + 12 h)
Cold
Change of temperature
Salt spray test
58
Reference Standard
IEC 61000-4-8, Level 4
IEC 62689-1
IEC 61000-4-9, Level 4
IEC 62689-1
IEC 61000-4-10, Level 4
IEC 62689-1
IEC 61000-4-3, Level 3
IEC 62689-1
IEC 61000-4-6, Level 3
IEC 62689-1
IEC 61000-4-16
IEC 62689-1
Reference Standard
IEC 61326-1
CISPR32
IEC 61326-1
CISPR32
Reference Standard
IEC 60068-2-2
IEC 62689-1
IEC 60068-2-78
IEC 62689-1
IEC 60068-2-30
IEC 62689-1
IEC 60068-2-1
IEC 62689-1
IEC 60068-2-14
IEC 60068-2-11
Test Requirement
30 A/m (continuous field) and
300 A/m pulsed (short duration for
3 s) on the X, Y, Z axis of the
product
Performance criterion: A
300 A/m pulsed on the X, Y, Z axis
of the product
Performance criterion: B
Oscillation frequency: 0.1 MHz and
1 MHz
Repetition rate: 40 transients/s at
0.1 MHz, 400 transients/s at 1 MHz
Test duration: 2 s
30 A/m peak
Performance criterion: B
10 V/m (80 MHz to 2.7 GHz) and
3 V/m (2.7 GHz to 6 GHz)
Performance criterion: A
Frequency: 0.15 MHz to 80 MHz
Modulation: 80 % AM; 1 kHz
Test Voltage: 10 Vrms
Performance criterion: A
30 V continuously
300 V for 1 s
Performance criterion: A
Test Requirement
150 kHz to 30 MHz (Class A)
30 MHz to 6 GHz (Class A)
Test Requirement
+ 75° C; duration: 16 h (with device
turned OFF) + 16 h (with device
turned ON)
(40 ± 2)° C; 98 % RH; duration:
4 days (with device turned OFF) +
4 days (with device turned ON)
25° C to 40° C. 98 % RH, duration:
21 days
-20° C; duration: 16 h (with device
turned OFF) + 16 h (with device
turned ON)
+75° C & -20° C, 0 % RH
3 h + 3 h, 5 cycles
96 h, NaCl 5 % with DM water
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022