2.2
Hardware Components
The device consists of the following hardware components:
LEDs
The device consists of 3 LEDs which indicate the status as follows:
Fault LED (Red)
Indicates when a ground-fault is detected
Battery LED (Amber)
Indicates the health of the battery on pressing of the push-button
Auxiliary LED (Green)
Indicates that the device is operating on the auxiliary voltage
Flag indicator - The device consists of 1 flag indicator for indicating the ground-fault.
Binary output (BO)
The device consists of the following binary outputs:
Ground-fault BO
The device has 2 binary output contacts (1 changeover (CO) type + 1 normally open (NO) type
spare) for indicating the ground-fault status remotely to SCADA via FRTU/RTU.
Battery Health BO
The device also has 1 dedicated binary output (NO type) for indicating battery health state remotely
to SCADA via FRTU/RTU.
Signal Lamp BO
The device comes with a signal lamp BO for connecting to Siemens signal lamp accessory for
ground-fault indication.
For more information on device binary outputs, refer to 5.5 Binary Outputs.
DIP switch - The DIP switch is used for configuring the response time, auto reset time, and other settings.
For more information about DIP the switch, refer to 5.4.1 DIP Switch Overview .
Fault reset inputs - The device consists of fault reset inputs for resetting the fault indication in the device
via the push-button, AC/DC BI reset, and remote reset. For more information on the various fault reset
options, refer to 5.2 Fault Reset .
Push button - The push-button is used for resetting the fault indication by the device manually, for
executing the function check (Fn Chk) and battery check (Batt Chk). For more information on push-
button, refer to 5.3 Push Button.
Only available in dual-powered SICAM EFI variants.
1
2
Only available in 6MD2311-1BB00-0AA3, 6MD2311-1BE00-0AB6, and 6MD2311-2BB10-0AA5 MLFB device variants
3
Not available in 6MD2311-1BB00-0AA3 and 6MD2311-1BE00-0AB6 MLFB device variants.
SICAM, Earth Fault Indicator, Manual