Siemens SICAM Manual page 53

Earth fault indicator
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Maximum carry current
Maximum switching current:
Operating Temperature
Table 4-3
Operating temperature and
Ambient storage temperature
Mechanical Data
Table 4-4
Dimensions (W x H x D)
Weight
Mounting position
Ground-Fault Current Range (for all sensors)
Table 4-5
Ground-Fault current range
Typical accuracy
Type 1 Sensor (for three-core cable)
Table 4-6
Sensor ∅
Sensor Wire Length
Current cable ∅ supported
Material
Type 2 Sensor (for three-core cable)
Table 4-7
Sensor ∅
Sensor Wire Length
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022
Operating Temperature
Mechanical Data
Ground-Fault Current Range for all sensors
Type 1 Sensor
Type 2 Sensor
2 A
0.25 A, AC 250 V/0.13 A, DC 220 V
Device
-20 ° C to +75° C
6MD2311-1BB00-0AA3
6MD2311-1BE00-0AB6
6MD2311-1DC00-0AB6
6MD2311-1DD00-0AB6
6MD2311-1DE00-0AB6
-30 ° C to +75° C
6MD2311-2BB10-0AA5
6MD2311-1DC10-0AB6
Signal Lamp
-30 ° C to +75° C
140 mm x 150 mm x 41 mm (with glands)
447 g
Surface-mounting position (on RMU panel or wall)
25 A to 100 A (For Type 1 sensor)
25 A to 240 A (For Type 2, Type 3 and Type 4 sensor)
±10% of the selected setting
150 mm
3.5 m, 5 m
60 mm to 150 mm
Flexible insulated and UV stabilized material
140 mm
16 m
Product Specifications