By default, the auxiliary AC recovery reset setting is Disable.
NOTE
i
i
The auxiliary AC recovery reset feature is available in SICAM EFI with AC supply input variants only
(6MD2311-1DC00-0AB6, 6MD2311-1DC10-0AB6, 6MD2311-1DD00-0AB6, and 6MD2311-1DE00-0AB6).
Response Time
5.4.5
The response time is the minimum time that a fault current must persist in the network for a fault to be
termed as a valid fault. The response time for a valid fault is configured manually using the positions DIP 1 and
DIP 2 in DIP Switch (S4). The response time is different depending on the selected MLFB. The following tables
provide a detailed overview of the response time (in millisecond (ms)) of the device depending on the DIP
switch position.
Battery-Powered Variants: Response Time Settings
Table 5-3
DIP 1
OFF
OFF
ON
ON
Dual-Powered Variants: Response Time Settings
Table 5-4
DIP 1
OFF
OFF
ON
ON
Fault Auto-Reset Time
5.4.6
The fault auto-reset feature is used to reset fault indications automatically after a configured time period has
elapsed. The fault auto-reset time can be configured manually by using the positions DIP 3 and DIP 4 in
DIP Switch (S4). The fault auto-reset time is different depending on the selected MLFB. The following table
provides a detailed overview of the fault auto-reset time (in hours (h)) of the device depending on the DIP
Switch positions.
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022
Response Time Setting for Battery-Powered Variants
DIP 2
6MD2311-1BB00-0AA3
OFF
40 ms
ON
60 ms
OFF
80 ms (default)
ON
100 ms
Response Time Setting for Dual-Powered Variants
DIP 2
6MD2311-1DC00-0
AB6
OFF
50 ms
ON
80 ms
OFF
100 ms (default)
ON
150 ms
Auxiliary AC Recovery Reset
Disable
Enable
6MD2311-1BE00-0AB6
40 ms
60 ms
80 ms (default)
100 ms
6MD2311-1DC10-0
6MD2311-1DD00-
AB6
0AB6
50 ms
50 ms
80 ms
80 ms
100 ms (default)
100 ms (default)
150 ms
150 ms
Device Functions
5.4 DIP Switch
6MD2311-2BB10-0AA5
40 ms
60 ms
80 ms (default)
160 ms
6MD2311-1DE00-
0AB6
50 ms
80 ms
100 ms (default)
150 ms