Features - Siemens SICAM Manual

Earth fault indicator
Hide thumbs Also See for SICAM:
Table of Contents

Advertisement

Overview
2.3 Features
2.3

Features

The salient features of SICAM EFI are mentioned as follows:
Power ON options
Self-sustained using internal Li-SOCl
Dual-powered using auxiliary (AC/DC) power supply
Safety
The device complies with the IEC 61010-1 safety standards
Simple
Supports easy device configuration using DIP switch based settings
Configurable and changeover type binary outputs
Configurable ground-fault binary output as latch/wipe type
Providing remote indications of ground fault and battery health via FRTU/RTU
Self-test diagnostic
Supports self-test locally using the push-button and remotely using the Low-Voltage Reset (LVR) contact.
Local indication
1 red LED and 1 red mechanical flag
1 green LED for AC/DC auxiliary power status
1 amber LED for battery health status
1 signal lamp output for local ground-fault indication
Multiple fault reset functionality
Remote reset/Low-voltage reset (LVR), push-button reset, AC/DC voltage reset via binary input, Auxiliary
AC recovery reset, ground current-based reset, auto reset using timer.
Extended battery life
Enhanced power management leading up to 2000 h of fault indication operation (single blink/second).
Ground-fault indication pattern
Simple blinking pattern for easier identification of fault current.
Single blink pattern: Fault current was present.
Double blink pattern: Fault current is still present.
Certifications
Complies with IEC 62689-1 standard for short circuit indicators.
Complies with IEC 61869-1, 61869-2, 61869-10 standard for sensors.
Sensors
Split core sensors with easy locking mechanism. Retrofit on three-core/single-core cable along with
3.5 m, 5 m, and 16 m wire length. The sensor wire length options are MLFB-specific, refer 2.5 Ordering
Information (MLFB Details) for more information.
Built-In Restraints
Avoids false fault detection due to ground-current inrush and auto-reclosure operations.
4
Only available in dual-powered device variants.
5
Only available in selected device variants (MLFB 6MD2311-2BB10-0AA5 and 6MD2311-1DC10-0AB6)
14
 battery
2
4
5
 for indicating ground fault.
4
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022