Advertisement

3.5
Mounting of the Ground Sensor on Single-Core Cables: Use Cases
For accurate mounting of ground sensor on single-core cables, ensure that the ground sensor is mounted as
per the following mounting methods:
Mounting Method 1:
For end-to-end cable distance of 220 mm, the sensor is mounted such that the belt is inserted up to the
stopper. Refer to Figure 3-11.
Mounting Method 2:
For end-to-end cable distance of 340 mm, the sensor is mounted such that the belt is inserted up to the
marker line on the belt. Refer to Figure 3-11. The stopper position is displaced by approximately 30 mm
in this case.
NOTE
i
i
Whenever the end-to-end cable distance is between 220 mm to 340 mm, you can tighten the sensor belt to
an appropriate location between the stopper and the marker line.
[dw̲efisinglecore?usecases, 1, en̲US]
Figure 3-11
(1)
End-to-end cable distance (220 mm to 340 mm)
(2)
Line marker for 340-mm end-to-end cable distance
(3)
Stopper position for 220-mm end-to-end cable distance
SICAM, Earth Fault Indicator, Manual
E50417-H8940-C600-A3, Edition 12.2022
Ground Sensor Mounting on Single-Core Cable Depending on End-to-End Cable Distance
3.5 Mounting of the Ground Sensor on Single-Core Cables: Use Cases
Installation and Commissioning
35