Omron SYSDRIVE RV Series User Manual page 153

High-function general-purpose inverters
Table of Contents

Advertisement

Motor 2 V/f Pattern: E3
User parameters for motor 2 V/f characteristics are shown in the following table.
Param-
eter
Num-
ber
Motor 2
control
method
E3-01
selection
Control
Method
Motor 2
max. out-
put fre-
quency
E3-02
(FMAX)
Max Fre-
quency
Motor 2
max. volt-
age
E3-03
(VMAX)
Max Volt-
age
Motor 2
max. volt-
age fre-
quency
E3-04
(FA)
Base Fre-
quency
Motor 2
mid. out-
put fre-
quency 1
E3-05
(FB)
Mid Fre-
quency
Motor 2
mid. out-
put fre-
quency
E3-06
voltage 1
(VC)
Mid Volt-
age
Motor 2
min. out-
put fre-
quency
E3-07
(FMIN)
Min Fre-
quency
Motor 2
min. out-
put fre-
quency
E3-08
voltage
(VMIN)
Min Volt-
age
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when the control method is changed. The V/f control factory settings are given.
* 3. When C6-01 = 1, the upper limit is 400.0.
-36
5
Name
Description
Display
0: V/f control
1: V/f control with PG
2: Open-loop vector control
3: Flux vector control
Output voltage (V)
Frequency (Hz)
To set V/f characteristics in a
straight line, set the same values
for E3-05 and E3-07.
In this case, the setting for E3-06
will be disregarded.
Always ensure that the four fre-
quencies are set in the following
manner:
E3-02 (FMAX) ≥ E3-04 (FA) >
E3-05 (FB) > E3-07 (FMIN)
Control Methods
Change
Setting
Factory
during
Range
Setting
Opera-
V/f
tion
0 to 3
0
No
A
40.0 to
60.0
No
A
300.0
Hz
*3
0.0 to
200.0
No
A
255.0
V
*1
*2
0.0 to
60.0
No
A
300.0
Hz
*3
0.0 to
3.0 Hz
No
A
300.0
*2
*3
0.0 to
15.0 V
No
A
255.0
*1
*1
0.0 to
1.5 Hz
No
A
300.0
*2
*3
0.0 to
9.0 V
No
A
255.0
*1
*1
Regis-
V/f
Open
Flux
Page
ter
with
Loop
Vec-
PG
Vector
tor
A
A
A
319H
-
A
A
A
31AH
-
A
A
A
31BH
-
A
A
A
31CH
-
A
A
No
31DH
-
A
A
No
31EH
-
A
A
A
31FH
-
A
A
No
320H
-

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

3g3rv-v1

Table of Contents