Countermeasures Against Radio Interference
Radio noise is generated from the Inverter as well as from the input and output lines. To reduce radio noise,
install noise filters on both input and output sides, and also install the Inverter in a totally enclosed steel box.
The cable between the Inverter and the motor should be as short as possible.
Cable Length between Inverter and Motor
If the cable between the Inverter and the motor is long, the high-frequency leakage current will increase, caus-
ing the Inverter output current to increase as well. This may affect peripheral devices. To prevent this, adjust
the carrier frequency (set in C6-01, C6-02) as shown in Table 2.8. (For details, refer to Chapter 5 Parameters.)
Cable length
Carrier frequency
Restriction on Using Single-phase Motors
Single-phase motors are not suited for variable-speed operation using the Inverter. There are two methods
used to determine the operating direction for a single-phase motor upon startup: Capacitor startup and split-
phase startup. With the capacitor startup method, there is a possibility that the steep charge and discharge of
the Inverter output will damage the capacitor. Likewise, with the split-phase startup method, there is a possi-
bility of damaging the starting coil because there is no centrifugal switch operation.
Ground Wiring
Observe the following precautions when wiring the ground line.
Always use the ground terminal of the 200-V Inverter with a ground resistance of less than 100 Ω and that
of the 400-V Inverter with a ground resistance of less than 10 Ω.
Do not share the ground wire with other devices, such as welding machines or power tools.
Always use a ground wire that complies with technical standards on electrical equipment and minimize the
length of the ground wire.
Leakage current flows through the Inverter. Therefore, if the distance between the ground electrode and the
ground terminal is too long, potential on the ground terminal of the Inverter will become unstable.
When using more than one Inverter, be careful not to loop the ground wire.
-22
2
Steel box
Power
MCCB
supply
Noise
Inverter
filter
Fig 2.13 Countermeasures Against Radio Interference
Table 2.8 Cable Length between Inverter and Motor
50 m max.
15 kHz max.
OK
Fig 2.14 Ground Wiring
Metal pipe
Noise
IM
filter
100 m max.
10 kHz max.
NO
More than 100 m
5 kHz max.