If The Motor Operates Higher Than The Reference; If The Slip Compensation Function Has Low Speed Precision; If There Is Low Speed Control Accuracy At High-Speed Rotation In Open-Loop Vector Control Method; If Motor Deceleration Is Slow - Omron SYSDRIVE RV Series User Manual

High-function general-purpose inverters
Table of Contents

Advertisement

If the Motor Operates Higher Than the Reference

Use the following information if the motor operates higher than the reference.
The analog frequency reference bias setting is wrong (the gain setting is wrong).
The frequency reference bias set in parameter H3-03 is added to the frequency reference. Check to be sure that
the set value is suitable.
A signal is being input to the frequency reference terminal A2 or A3.
When 0 (Add to terminal A1) is set for parameter H3-09 (Multi-function Analog Input Terminal A2 Function
Selection) or H3-05 (Multi-function Analog Input Terminal A3 Function Selection), a frequency correspond-
ing to the terminal A2 or A3 input voltage (current) is added to the frequency reference. Check to be sure that
the set value and analog input value are suitable.

If the Slip Compensation Function Has Low Speed Precision

If speed control accuracy is low for the slip compensation function, the slip compensation limit has been
reached. With the slip compensation function, compensation cannot be carried out beyond the slip compensa-
tion limit set in parameter C3-03. Check to be sure that the set value is suitable.
If There is Low Speed Control Accuracy at High-speed Rotation in Open-
loop Vector Control Method
The motor's rated voltage is high.
The Inverter's maximum output voltage is determined by its input voltage. (For example, if 200 VAC is input,
then the maximum output voltage will be 200 VAC.) If, as a result of vector control, the output voltage refer-
ence value exceeds the Inverter output voltage maximum value, the speed control accuracy will decrease. Use
a motor with a low rated voltage (i.e., a special motor for use with vector control), or change to flux vector
control.

If Motor Deceleration is Slow

Use the following information when the motor deceleration is slow.
The deceleration time is long even when braking resistor is connected.
The following causes are possible.
"Stall prevention during deceleration enabled" is set.
When braking resistor is connected, set parameter L3-04 (Stall Prevention Selection during Deceleration) to 0
(disabled) or 3 (with braking resistor). When this parameter is set to 1 (enabled, the factory setting), braking
resistor does not fully function.
Troubleshooting
23