Using A Braking Unit And Three Braking Resistor Units In Parallel - Omron SYSDRIVE RV Series User Manual

High-function general-purpose inverters
Table of Contents

Advertisement

Using a Braking Unit and Three Braking Resistor Units in Parallel

This example shows wiring for using three Braking Resistor Units in parallel.
3-phase power
380 to 480 V
50/60 Hz
Overload relay trip contact
of Braking Resistor Unit
-22
10
A sequence is required to turn OFF the
power supply for the thermal overload relay
trip contacts of the Braking Resistor Unit.
MCCB
Fault contacts
Forward Run/Stop
Reverse Run/Stop
Braking Unit
External fault
* Disable stall prevention during deceleration by setting L3-04 to Resistor Unit. The motor may
not stop within the deceleration time if this setting is not changed.
Thermal
protector
Thermal switch
R/L1
U/T1
Inverter
V/T2
S/L2
W/T3
T/L3
Cooling fan
Voltage
setting
Fault contact output
Forward run com-
mand (forward run
when ON)
Reverse run com-
mand (reverse run
when ON)
Fig 10.12
Thermal
Thermal
protector
protector
Braking
Braking
Resistor
Resistor
Unit
Unit
Braking Unit
Motor
Ground to 10 Ω max.
Braking
Resistor
Unit