Installation

18.2
Siemens Industry, Inc.
Building Technologies Division
The releasing module XCI2001-U1 is installed on the periphery board as shown and
screwed onto the back box. Slot X901 is also used for the NAC module (1A/2B).
Installation of releasing module on the periphery board
1
Periphery board (252p) or periphery board (504p)
2
Threaded sleeves on back box
3
Releasing module XCI2001-U1
4
2x fixing screw
X901
Slot in periphery board
X5
Connection terminal on releasing module
1.
Plug the releasing module (3) into slot X901 on the periphery board.
2.
Fasten the releasing module to the threaded sleeves (2) in the back box using
the two fixing screws (4).
3.
Wire up the releasing module according to the pin assignment.
FS20 Marine Fire Detection Control Panel
99
A6V10519176_enUS_b