Notification Appliance Circuits

12.2
The following wiring diagrams displays the process to connect notification devices to
the circuit, either as class A (style Z) or class B (style Y) circuit. For class A, no end-of-
line resistor is required. It is built into the circuit.
To ensure proper functioning, the jumpers must be set correctly for class A/B
selection.
Polarity shown is in activated condition.
Notification appliance circuit supervised and power limited.
X601: Class A (style Z) supervised output connection
X601: Class B (style Y) supervised output connection
* EOL resistance must be connected during non-use.
EOL resistance: 2.4 kΩ, 0.5 W
See also
Siemens Industry, Inc.
Building Technologies Division
NAC1-1
NAC1-1
NAC1-2
NAC1-2
NAC1-1
NAC1-1
NAC1-2
NAC1-2
X602 Jumper – DEGRADED MODE ENABLE/DISABLE for NAC 1 class A or NAC 1-1
class B
X603 Jumper – DEGRADED MODE ENABLE/DISABLE for NAC 1-2 class B
X604, X605, X606 Jumper – NAC 1 class A/B
FS20 Marine Fire Detection Control Panel
X601
+
+
4
-
-
3
+
2
-
1
X601
+
+
4
-
-
3
+
*
2
EOL
-
1
+
-
+
EOL
-
A6V10519176_enUS_b
61