FS20 Marine Fire Detection Control Panel
Adjustment Elements
19.5
Reset key S2
The reset key S2 has two functions:
DIP switch S1
All switches are set to the OFF position (right-hand position) at the factory.
View of DIP switch S1 with inscription
S1 switch Designation
8
PWR_F
7
SW_REV
6
1
5
0
4
8
3
4
2
2
1
1
108
Siemens Industry, Inc.
Building Technologies Division
Restart the processor to trigger the watchdog
Read-in the set baud rate and address with DIP switch S1
PWR_F
SW_REV
1
BAUD
0
8
4
ADR
2
1
Function
Third voltage source (not required for UL)
Baud rate
Device address
Position Definition
ON
Switches the third voltage source on
OFF
Third voltage source is not connected
(default)
ON
Activates the software update mode
OFF
Normal operation (default)
Baud rate setting according to table below
Address setting according to table below. Every
device must have a separate address. The first
device must have the address 1.