19.4
The circuit must not be terminated on the side of the RS-485 class 'A' module,
because the RS-485 class 'A' module has integrated terminating resistors.
When wiring as a class 'B' circuit, the circuit on the last device must be terminated
with a 120 Ω resistor.
Wiring from the Remote Terminal to the RS-485 Circuit as A Class 'B'
Circuit
FT2015 class B, style 4 wiring
106
Siemens Industry, Inc.
Building Technologies Division
Des.
Function
X3
Connection for ribbon cable to display
X4
Connection for ribbon cable to display
X5
Connection plug for supply and 'NET_OUT' circuit output
X6
Connection plug for input supply and 'NET_IN' line input
X11
Connection for key switch
S1
DIP switch, 8-pole, for address setting and other functions
S2
Reset key
H1...H29
LED indicators, front
A6V10519176_enUS_b