Commissioning with Auto-Configuration without a PC
25.7
This procedure applies to standalone 'Panels' only
With commissioning variant, a 'Panel' is commissioned without a PC and the configuration tool.
Prerequisites:
The detector circuits and devices are installed.
•
The detector circuits and devices are configured and tested with the 'Device Programming
•
Unit' DPU.
The 'Panel' is installed.
•
The batteries are installed, but not connected.
•
The cables for the detectors circuits and mains supply have been fed into the 'Panels' and are
•
not connected.
Commissioning
1. Prepare the 'Panel' for commissioning.
2. Perform the auto-configuration
3. Adapt the auto-configuration on the Operating Unit.
4. Test the function of the 'Site' and rectify errors if necessary.
5. Perform the completion work.
Adding a 'Panel' to an Existing Site
25.8
Prerequisites:
•
•
•
•
•
•
•
Siemens Industry, Inc.
Building Technologies Division
'Auto-configure Panel' or
•
Individually auto-configure detector circuits.
•
Change customer texts
•
Set the properties of the devices.
•
The detector circuits and devices are installed.
The detector circuits and devices are configured and tested with the 'Device Programming
Unit' (DPU)
The 'Panel' is installed.
The batteries are installed but not connected.
The cables for the detector circuits and mains supply have been fed into the 'Panel', and
not connected.
The configuration tool is installed on the PC.
The current firmware and BDV are available on the PC.
FS20 Marine Fire Detection Control Panel
123
A6V10519176_enUS_b