FS20 Marine Fire Detection Control Panel
Properties of the 'SAFEDLINK Interface (FN2001-U1)' Element
The following is set in the detail editor of the 'SAFEDLINK interface (FN2001-U1)' element
for fire only devices:
'Suppress port troubles': You can use this property to configure a SAFEDLINK connection as
a class B circuit. To do this, first select the 'Port 1 troubles' setting in the first 'Panel' of the
SAFEDLINK connection. In the last 'Panel', select the 'Port 2 troubles' setting.
If you configure the SAFEDLINK connection as a class A circuit, select the ' - (none)' setting.
If the ' - (none)' setting is selected, troubles arise when wiring as a class B circuit.

Indicators

15.6
LED
Color
H1
Green
H2
Yellow
H3
Yellow
84
Siemens Industry, Inc.
Building Technologies Division
Properties in the detail editor of the SAFEDLINK interface
Function
Condition
Condition of the
Off
network module
On
(SAFEDLINK)
Flashes
Status of circuit 1
Off
(A1, B1)
On
Status of circuit 2
Off
(A2, B2)
On
Definition
Network module (SAFEDLINK) is defective
Normal condition (H2 and H3 are off)
Normal condition for degraded mode module (H2 and H3 are off)
Normal condition
(communication on circuit 1 is OK)
Error on circuit 1
(no communication on circuit 1)
Normal condition
(communication on circuit 2 is OK)
Error on circuit 2
(no communication on circuit 2)
A6V10519176_enUS_b