Indicators

6.7
LED
Color
Function
H37
Yellow
Diagnosis 1
H38
Yellow
Diagnosis 2
H39
Yellow
Diagnosis 3
H50
Yellow
'MSP fail' (processor periphery)
H51
Red
'PD ready', installation ready to
switch off
H52
Yellow
'PPC fail' (CPU module)
H53
Yellow
'CPLD fail' (reset and watchdog
logic)
H54
Red
'TEMP', CPU module excess
temperature indicator
H61
Yellow
'SPEED', Ethernet transmission
indicator
H842
Green
'LINK' control indicator
Siemens Industry, Inc.
Building Technologies Division
FS20 Marine Fire Detection Panel Control Panel
Condition
Definition
Off
Normal operation
On
Ground fault present
Not used
Not used
Off
Normal operation
On
Processor in degraded mode; replace component or
contact hotline
Off
Installation in operation
On
Installation may be disconnected from the mains
Off
Normal operation
On
Processor in degraded mode; replace component or
contact hotline
Off
Normal operation
On
Logic unit failed; replace component or contact hotline
Off
Normal operation
On
CPU >45 °C
Off
Data transfer at 10 Mbit/s
On
Data transfer at 100 Mbit/s
Off
No Ethernet connection
On
Ethernet connection established