Preparing The 'Panel' For Commission ~ Without Base Data Variant (Bdv) Installation; Auto-Configuring 'Panel; Auto-Configuring The Detector Circuits - Siemens FC2025 Manual

Fire alarm control panel marine application
Hide thumbs Also See for FC2025:
Table of Contents

Advertisement

Preparing the 'Panel' for Commission ~ without Base
25.2
Data Variant (BDV) Installation
The following steps are not necessary to install the BDV for the further procedure. This is used to
save having to restart the panels.
1. Connect the cables for the detectors circuits and the periphery devices.
2. Connect the power supply (mains and batteries).
3. Wait until the display indicates the selection of the BDV.

Auto-Configuring 'Panel'

25.3
1. Select 'Topology' > 'Hardware tree' > 'Panel' in the main menu.
2. Press the 'MoreOptions' softkey and select 'Execute Commands'.
3. Select the 'Auto-configure panel' command.

Auto-Configuring the Detector Circuits

25.4
NOTICE
Incorrect Order For Reading In A Class A Circuit
Error when reading in a class A circuit
The detector circuits are detected as class B during the first system start-up, e.g. 'Circuits' 11, 'Circuit
12 (2-digit circuit number) even if they are connected as a class A circuit.
1. Select 'Topology' > 'Hardware tree' > 'Panel' > 'Circuit card' > Detector circuit in the main menu.
2. Press the 'MoreOptions' softkey and sleets 'Execute commands'.
3. Select the 'Auto-configure circuit' command.
The detector circuit is auto-configured.
A message is displayed following a successfully auto-configuration: 'Command executed',
Siemens Industry, Inc.
Building Technologies Division
The 'Panels' start and reads in the internal hardware.
During the start-up, the 'Trouble' LED flashes and the display shows the progress.
During the start-up, the firmware version F-FXS2001 is displayed.
The 'Panel' is prepared for commissioning.
The 'Panel' is auto-configure.
A message is displayed following a successful auto-configuration: 'Command execute'.
Always select the first 'Circuit' to read in a class A circuit, in this case, 'Circuit 11. 'Circuit' 12
is then read in automatically. After reading in Class A circuit is indicated with a 1-digit number,
in this case, as 'Circuit' 1.
Proceed in the same way from 'Circuit' 21/22 (class A circuit 2) to 'Circuit' 41/42 (class A
circuit 4).
FS20 Marine Fire Detection Control Panel
119
A6V10519176_enUS_b