Siemens FC2025 Manual page 55

Fire alarm control panel marine application
Hide thumbs Also See for FC2025:
Table of Contents

Advertisement

Properties
The power supply connects to (170W) FP2011-U1 with a maximum load of 6.5 A.
 The battery charger capable of charging up to 100 Ah batteries at a maximum of
6A.
 Power supply (170W) FP2011 must be used for batteries of 33 Ah or less.
 Ground faults detected at <1 kΩ to ground.
 Ground fault detection for all circuits except the two detector circuits handled by
Operating Unit. Each detector core has its own ground fault and supervision
circuit.
 Two integrated network circuit cards, one for circuits 1 and 2, one for circuits 3 and
4, and EMC surge protection for eight style 4 or four style 6 circuits.
 Maximum of 252 device addresses can be controlled per integrated network circuit
card.
 Three relay outputs and one user programmable relay output for common alarm,
common trouble, common supervision and user programmable.
 The auxiliary output is a regulated 24VDC output with a maximum of 1.5 A.
 Degraded alarm and trouble mode functions when either or both CPUs for the
periphery board or Operating Unit are compromised.
 Integrated NAC circuits, specified for 24VDC, configured for either one class A
(style Z) or two class B (style Y) circuits with a maximum of three A for one class A
or one of the two class B circuits. NACs have integrated synchronization protocol
for audible or visual notification appliances.
All NAC circuits are supervised and protected for over current and direct short-
circuited output.
Two slots for optional extensions, one of which is for NAC module (1A/2B) or
releasing module (XCI2001-U1):
NAC module (1A/2B) FCI2001-U1 for one additional class A circuit or two class
B circuits (same data as integrated NAC circuits) (P/N S54400-A54-A1). The
module connects to X901.
Releasing module (XCI2001-U1) (P/N S54400-A69-A1) The module connects
to X901.
Additional peripheral data bus connection (X202) for LED or DACT modules.
Main CPU and detector core CPUs capable of being updated in the field through
the Operating Unit.
Siemens Industry, Inc.
Building Technologies Division
FS20 Marine Fire Detection Control Panel
55
A6V10519176_enUS_b

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fc2050Fc922Fc924

Table of Contents