FS20 Marine Fire Detection Control Panel
Adjusting Elements for Releasing Module
18.6
Button
Function
S1
Arming of releasing 1
S2
Arming of releasing 2
S1 and S2 Control Output
S3, Reset Key for Releasing Module
Button
Function
S3
RESET
18.6.1 Jumper X3, Degraded Mode Enable for Releasing
X3
Jumper position
3 - 2
3
1 - 2
2
1
Jumper X3 must agree with the panel configuration or a trouble will be displayed.
Technical Data
18.7
Supply input
Connection terminals
Mechanical data
102
Siemens Industry, Inc.
Building Technologies Division
S1 and S2, Switches to Arm/Disarm the Releasing Outputs
Position
OFF
ON
OFF
ON
The outputs are disarmed in the OFF position. The relays are disarmed and
supervised.
The outputs are armed in the ON position.
Position
Pressed
Function
Activated
Deactivated
Voltage
Quiescent current
Output voltage
Output current
Design
Admissible cable cross-section
Dimensions (W x H)
Weight
Definition
Releasing output 1 disarmed (supervisory mode)
Releasing output 1 armed (normal)
Releasing output 2 disarmed (supervisory mode)
Releasing output 2 armed (normal)
Definition
The module is reset
Definition
No degrade operation allowed (Default)
Degrade operation allowed
24VDC
11 mA at 24VDC
24VDC Special Application
2.0 A per output channel
Screw terminals
12 AWG...18 AWG, not shielded
3.25 x 4.75 inches
Approx. 90 g
A6V10519176_enUS_b