Technical Data

12.9
Supply Input
Battery
NAC Circuit
AUX Output
Bell Follower Input
Siemens Industry, Inc.
Building Technologies Division
Plug strip
Operating voltage
Operating current (standby)
Max. operating current.
Input current (active)
Design
Plug strip
Voltage
Current
Plug strip
Voltage
Standby operating current
Active operating current
Maximum circuit resistance
Supervised for
Design
Plug strip
Voltage
Current
Design
Plug strip
Voltage
Current
Design
FS20 Marine Fire Detection Control Panel
X301
24VDC nominal, filtered
120 mA
136 mA
6.5 A for PS170W, 11.5 A for 1 PS300W
Non-power limited
X303
DC 20.4...26.4 V
11.5 A
X601
24VDC
Special Application for strobe loads
Regulated for non-pulsing loads
Max. 10 mA
3 A (for a class A circuit or per class B circuit)
1.4 Ω @ 3.0 A
Open circuit
Short circuit
Ground fault
Short-circuit protection
Voltage surge protection
Power limited
X1001
24VDC nominal "Special Application"
For use with: HZM, HCP, FCA2018-U1, FT2015-U1,
FTI2001-U1
Max. 1.5 A
Short-circuit protection
Voltage surge protection
Power limited
X1001
24VDC filtered or full wave
Max. 4 mA
Voltage surge protection
69