Element
Fuses
Indicators
Adjustment elements
Jumper
Connector
Siemens Industry, Inc.
Building Technologies Division
Destination
Function
F301
30 A fuse for battery
H1301
Status display for circuit card 1 (circuits 1 and 2)
S100
Reset key for periphery processor (without circuits)
S1201
Reset key for circuit card 1 (circuits 1 and 2)
X403
Degraded mode ALARM SILENCEABLE/NON SILENCEABLE
X602
Degraded mode ENABLE/DISABLE NAC 1 class A or NAC 1-1 class B
X603
Degraded mode ENABLE/DISABLE NAC 1-2 class B
X604
NAC 1 class A/B selection
X605
NAC 1 class A/B selection
X606
NAC 1 class A/B selection
X305
Power supply 2 ON/OFF
X201
Peripheral data bus to the Operating Unit & Mainboard
X202
Peripheral data bus output
X204
Future extension (not used)
X301
Connector for power supply 1 (PS1)
X302
Not connected
X303
Battery connection
X304
Not connected
X601
NAC1 output
X801
BELL follower input
X901
NAC 2 extension or releasing module
X902
For future application
X1001
Output 24VDC AUX
X1101
Plug block for relay connections
X1302
For future application
X1401
Detector circuit card 1, circuit 1
X1402
Detector circuit card 1, circuit 2