Mitsubishi CR800 Series Instruction Manual page 70

Table of Contents

Advertisement

1Error list
Error No.
H7652 *
Error message Force sense I/F unit revision illegal
Cause
Measures
H766n
Error message The force sensor data exceeded the tolerance value.
(n indicates the
Cause
sensor axis.)
Measures
H7700 *
Error message CC-Link card is illegal (Error Code).
Cause
Measures
H7710 *
Error message Cannot set a CC-Link master station.
Cause
Measures
H7720 *
Error message Two CC-Link interface cards are mounted.
Cause
Measures
L7730
Error message CC-Link data link error (local station connection error)
Cause
Measures
L7750
Error message A (CC-Link) cable is not connected or parameters do not match.
Cause
Measures
H7760 *
Error message CC-Link initialization error
Cause
Measures
L7780
Error message A CC-Link register number is outside the range.
Cause
Measures
L7781
Error message A signal number for CC-Link was specified.
Cause
Measures
H7810
Error message MONPORT/SLMPPORT parameter error
Cause
Measures
H7820
Error message Mxt Scommand timeout
Cause
Measures
H7830
Error message "Ethernet card is not installed, or command disable"
Cause
Measures
H7840
Error message Mxt command Illegal received data
Cause
Measures
H7860
Error message SLMP error
Cause
Measures
1-61
Error no. H7652 *
This force sense I/F unit revision is not supported.
Contact the maker.
The force acting on the force sensor exceeded the set tolerance value.
Check whether too large a force is acting on the force sensor.
Check whether an appropriate value has been set for parameter FSLMTMX.
Refer to the section "Force Sensor Tolerance" in separate manual, "Instruction Manual/Force Sense
Function" for details on the error recovery method.
CC-Link card is illegal.
Please exchange the CC-Link card. When it comes back, contact to the dealer.
A master station is already set by the rotary switch.
Set the rotary switch to other than 0.
Mount one card in slot 2.
It is not allowed to install two cards. Install only one card.
There is a line error or the master station's parameter settings are invalid.
Review the line and parameters.
A cable is not connected or parameters do not match.
Reset the power and start again.
The master station's parameters do not match.
Correct the parameters, and then start again.
A register number entered is outside the allowable range.
Enter the correct value.
A signal number for CC-Link was specified.
Install a CC-Link interface card.
The element of MONPORT(1/2) and SLMPPORT overlap.
Please set not to overlap to another port number.
The setting time of the MXTTOUT parameter has been exceeded.
Make the MXTTOUT parameter value larger.
Ethernet card is not installed, or command disable.
Install Ethernet interface card.
The command argument and the data type do not match.
Check the command and the data you are sending.
An error related to SLMP has occurred.
Please confirm the content by a detailed number of the error.
Error cause and measures