Error No.
H018m
Error message Fuse is blown.(PIO) (Slot m-Fn)
(m=1 ~ 2)
Cause
Measures
Details
H0210 *
Error message Power supply error (***)
Cause
Measures
H0211 *
Error message Power supply error (***)
Cause
Measures
H0212 *
Error message Power supply error
Cause
Measures
H0213 *
Error message Power supply error
Cause
Measures
H0214 *
One of the errors below is detected.
Please take measures corresponding to an error message.
Error message Set the power supply to 100V
Cause
Measures
Error message Set the power supply to 200V
Cause
Measures
Fuse is blown.(Parallel I/O interface)
Change fuse (Parallel I/O interface)
The electric fuse Fn (n= 1-4) of the parallel input output interface installed to the option slot m (m= 1-2) is
open.
Removes the cause by which the fuse open and replaces the fuse.
予備ヒューズ
The power supply output voltage is out of the specified range.
The output voltage of the power supply in the robot controller is the specified value or higher/lower. After
turning OFF the power, turn ON the power again to reset the error. If the same error recurs, contact the
manufacturer.
* The part where an error is detected is shown in "***" in the message.
24V, 5V, 3.3V, 2.5V, 1.8V, RCPU 1.5V, CCPU 1.5V, 1.2V, RCPU 1.15V, CCPU 1.15V, 1.1V, Ether 1V,
ServoM 1V, ServoS 1V
The power supply output voltage is out of the specified range.
The output voltage of the power supply in the robot CPU is the specified value or higher/lower. After turn -
ing OFF the power, turn ON the power again to reset the error. If the same error recurs, contact the man -
ufacturer.
* The part where an error is detected is shown in "***" in the message.
5V、 3.3V、 2.5V、 1.8V、 1.5V、 1.3V、 1.15V、 1V、 FPGA
The output of the power supply deviated from the specified range.
Turn the power OFF and ON once. After turning OFF the power, turn ON the power again to reset the
error. If the same error recurs, contact the manufacturer.
The output of the power supply deviated from the specified range.
Turn the power OFF and ON once. After turning OFF the power, turn ON the power again to reset the
error. If the same error recurs, contact the manufacturer.
The parameter is different from detected voltage
The detected power supply voltage is 100V, but the power supply voltage set in the parameter is 200V. Set
the voltage to 100V, then cycle the power. The power must be cycled for the change to take effect.
The parameter is different from detected voltage
The detected power supply voltage is 200V, but the power supply voltage set in the parameter is 100V. Set
the voltage to 200V, then cycle the power. The power must be cycled for the change to take effect.
Error cause and measures
Fuse
1Error list
Fuse F1
ヒューズF1
Fuse F2
ヒューズF2
Fuse F3
ヒューズF3
Fuse F4
ヒューズF4
Error no. H018m (m=1 ~ 2)