Optional Functions; 50131 Compliance Precautions - Interlogix xGenConnect NXG-4 Installation And Programming Manual

Hide thumbs Also See for xGenConnect NXG-4:
Table of Contents

Advertisement

Alarm list, disabled
Inhibit includes, all allowed except engineer reset, which must be disabled
Pending alarms, enabled
Swinger shunt ≥ 3
Report restore, on ACK
Line fault, enabled per path used
Line fault delay, 0 s
Refer to xGen Reference Guide for additional features, accessible at level 3.
For EN 50131-3 & T031, it is required to apply the following supervision settings
for wireless expanders:
Short supervision: 20 minutes
Long supervision: 2 hours
Smoke supervision: 4 hours
Caution:
When any option, any additional function or any additional zone type in
this section does not comply with the EN 50131 requirements, the EN 50131
compliance label must be removed from the system.

Optional Functions

Detection of storage device – failure
Detection of low output voltage
EN 50131 Compliance Precautions
Installation
In order to install an EN 50131 compliant system, please make sure that all
system components are EN 50131 compliant.
Programming
Make sure that all system settings are in line with regulatory compliance
guidelines.
Size of log / event history
For full EN 50131 Grade 2 compliance, the system must store at least
500 events.
Events are read-only, they cannot be deleted or altered by users of any level. At
least 500 mandatory events are stored in a separate memory location.
Mandatory events will be preserved and will not be overwritten by non-mandatory
events according to the EN 50131 standard. To view only mandatory events,
select Event History Filter > Mandatory.
14
xGenConnect Installation and Programming Guide

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents