NXG-8(E) Terminals
XGEN
LAN
LEARN
Z WAVE
TERM
-
BUS
+
12 V 7 Ah
NXG-7002(-SIM)
J11
J14
USBUP
ETHERNET
xGenConnect Installation and Programming Guide
LAN-, LAN+, NEG, POS: Terminals for xGenConnect
RS485 bus.
LAN-
LEARN: Enrollment button, hold down for 3 s to activate
LAN+
automatic device enrollment feature.
NEG
TERM: Term link for xGenConnect RS485 bus. A TERM
POS
link should be installed on the two furthest devices.
EARTH
EARTH, AC, AC: Connect transformer (16 VAC 1.5 A) to
AC
terminals for power.
AC
−BLACK, +RED: Connect leads to 12V Sealed Lead Acid
BELL+
backup battery.
BELL-
BELL+, BELL−: Connect to indoor 12 VDC siren or
DATA
COM
speaker.
POS
DATA, COM, POS: NetworX 3-wire bus for legacy
SMOKE-
modules and keypads.
COM
SMOKE-, AUX+: Two or four wire smoke detectors, NXG-
AUX+
8 supports two wire smoke detectors and will drop
ZONE 8
power to the SMOKE- terminal to perform smoke
COM
alarm verification.
ZONE 7
COM, AUX+: Terminal for aux power to zones.
ZONE 6
ZONE 1 to 8, COM – terminals to connect to zones.
COM
Supports single EOL, zone doubling, and dual EOL
ZONE 5
tamper monitoring.
ZONE 4
COM
J14: Ethernet WAN link header must be fitted if no
ZONE 3
communicator module is installed, and must be
ZONE 2
removed to accommodate communicator module.
COM
J11: Terminal to connect communicator module to
ZONE 1
xGenConnect.
AUX+
Ethernet: Connect Ethernet cable to RJ45 socket to
OUTPUT 4-
provide internet connectivity to xGenConnect.
OUTPUT 3-
J13: 5-pin connector used to upgrade and program
OUTPUT 2-
xGenConnect with USBUP-EUR-V2 tool.
OUTPUT 1-
TAMPER: Connect to panel box tamper.
AUX+: Terminal for auxiliary power to outputs.
OUTPUT 4: Open collector output switches to ground,
power output, by default inverted, can be assigned to
an Action.
OUTPUT 3: Open collector output switches to ground,
power output, by default inverted, can be assigned to
an Action.
OUTPUT 2: Open collector output switches to ground,
hold-off for outdoor siren, by default inverted, can be
assigned to an Action.
OUTPUT 1: Open collector output switches to ground,
hold-off for outdoor flash, by default inverted, can be
assigned to an Action.
19