Installation Space Requirements
• Position the unit on a horizontal surface.
Any tilt in the unit should be 3° or less to the horizontal.
• Where a wall or other obstacle is in the path of the outdoor unit's intake or exhaust airflow, follow the installation space
requirements below.
• For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.
Wall facing one side
More than
3-15/16 (100)
Side view
Walls facing three sides
More than
1-15/16 (50)
Outdoor Unit Installation
1.
Installing the outdoor unit
• When installing the outdoor unit, refer to "Precautions for Selecting a Location" and the "Outdoor Unit Installation
Diagram".
• If drain work is necessary, follow the procedures in "2. Drain work".
2.
Drain work
CAUTION
• In cold areas, do not use a drain socket, drain caps (1, 2) and a drain hose with the outdoor unit. (Drain water may freeze,
impairing heating performance.)
• If the drain port is covered by a mounting base or floor
surface, place additional foot bases of at least 1-1/4
inch (30mm) in height under the outdoor unit's feet.
1) Attach
B
2) Attach
A
• When attaching
frame, make sure to connect the drain hose to the
drain socket first.
5
01_EN_3P628775-3.indd
5
More than
13-3/4 (350)
47-1/4
(1200)
or less
More than
1-15/16 (50)
More than 3-15/16 (100)
More than 13-3/4 (350)
Top view
unit: inch (mm)
drain cap (1) and
C
drain cap (2).
drain socket.
A
drain socket to the bottom
Walls facing two sides
More
than
3-15/16
(100)
Top view
When installed as in the figure on the left, it is recommended to either
change the orientation of the outdoor unit outlet side or use the air direction
adjustment grille (sold separately).
B Drain cap (1)
C Drain cap (2)
A Drain socket
Air outlet side
Bottom frame
Drain cap
Pinch the bottom
frame in.
61
More than
More than
13-3/4
3-15/16 (100)
(350)
More than
13-3/4 (350)
More than
1-15/16 (50)
C Drain cap (2)
Bottom frame
A Drain socket
Hose (available commercially,
inner dia. 5/8" (16mm))
EDUS042101