Indoor unit · Liquid piping thermistor (Th2) Error (faulty connec-
C4
tion, cut wire, short circuit, fault)
Indoor unit · BEV unit, gas piping thermistor (Th3) Error (faulty
C5
connection, cut wire, short circuit, fault)
Indoor unit · Intake air thermistor (Th1) Error (faulty connection,
C9
cut wire, short circuit, fault)
Indoor unit · Outlet air thermistor (Th4) Error (faulty connection,
CA
cut wire, short circuit, fault)
CJ
Indoor unit · remote controller sensor error
E0
Outdoor unit · Safety device operation
E1
Outdoor unit · PC board assembly fault
E1
Outdoor unit · PC board assembly fault
E3
Outdoor unit · High-pressure switch fault
E4
Outdoor unit · Low-pressure switch fault
E9
Outdoor unit · Electric expansion valve motor (20E) error
Heat source unit · Intake water temperature inter-lock operation
EC
(fan operation)
EF
Outdoor unit · Ice thermal storage unit error
F3
Outdoor unit · Discharge piping temperature error
H3
Outdoor unit · High-pressure switch operation
H4
Outdoor unit · Low-pressure switch operation
Outdoor unit · Outdoor air thermistor (Th1)
H9
Error (faulty connection, cut wire, short circuit, fault)
Outdoor unit · Outdoor air thermistor (Th1)
H9
Error (faulty connection, cut wire, short circuit, fault)
HC
Outdoor unit · Water temperature sensor system error
Ice thermal storage unit error, ice thermal storage controller error,
HF
error in outdoor unit during ice thermal storage operation
HJ
Outdoor unit · water system fault
J1
Outdoor unit · pressure sensor error
Outdoor unit · Discharge piping thermistor (Th3)
J3
Error (faulty connection, cut wire, short circuit, fault)
Outdoor unit · Discharge piping thermistor (Th3)
J3
Error (faulty connection, cut wire, short circuit, fault)
Outdoor unit · Intake piping thermistor (Th4)
J5
Error (faulty connection, cut wire, short circuit, fault)
J6
Outdoor unit · Heat exchange thermistor (Th2) error
Outdoor unit · Heat exchange thermistor (Th2) error
J6
Error (faulty connection, cut wire, short circuit, fault)
J7
Outdoor unit · Header thermistor (Th6) error
JA
Outdoor unit · Discharge piping pressure sensor error
JC
Outdoor unit · Intake piping pressure sensor error
JF
Outdoor unit · Oil temperature sensor (Th5) system error
JH
Outdoor unit · Oil temperature sensor (Th5) system error
L0
Outdoor unit · Inverter system fault
L4
Outdoor unit · Inverter cooler fault
Outdoor unit · Ground circuit for compressor motor, short circuit,
L5
or power unit short circuit
168
EDUS042101
18
3P124623-1E