Technical Specifications Of The Ltop Overvoltage Protection Module - Siemens SIMATIC NET SINAUT ST7 System Manual

Station control system
Table of Contents

Advertisement

Introduction to the SINAUT ST7 system
2.6 LTOP overvoltage protection modules
2.6.2

Technical specifications of the LTOP overvoltage protection module

LTOP
Transmission paths
Transmission ratio
Transmission range
Frequency-dependent attenuation
Insulation resistance
Test voltage
Surge withstand capability
Normal discharge current i
Output voltage limitation at i
Telecontrol line attachment
Modem attachment
Installation location
Permitted ambient conditions
Operating temperature
Transport/storage temperature
Relative humidity
Construction
Dimensions (W x H x D) in mm
Weight
Degree of protection
Installation
74
Private transmission lines with or without loading coils
1 : 1; ± 5 % (e.g. 600/600 ohms in the voice band)
300 Hz to 35 kHz
Attenuation
[dB]
0.2
0.8
0.9
1.0
> 2000 Mohms
4 kV, 50 Hz, 10 s
6 kV/2 J to EN 60 099-1
(8/20 µs)
5 kA
sn
Approx. 15 V
sn
Screw terminals
Cross-section 0.2 – 4 mm
Cross-section 0.2 – 2.5 mm
Screw terminals (wire cross-section, see telecontrol line attachment) or RJ-
12 jack for Western plug
As close as possible to where cable enters building
0 °C through +60 °C
-40 °C through +70 °C
Max. 95 % at +25 °C
90 x 75 x 110 mm
LTOP1: 300 g
LTOP2: 320 g
OPM: 10 g
IP 20
DIN rail TS35 (35 mm; EN 50 022)
Frequency
[Hz]
MD100
1300 ... 3300
1200
5200 ... 8400
10,400 ... 16,800
20,800 ... 30,600
with rigid cores
2
with flexible cores
2
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06
Transmission speed [bps]
MD124
MD2
1200
1200
2400
2400
4800
9600
19,200
9600
19,200
MD3
All