Introduction to the SINAUT ST7 system
2.3 SINAUT TIM communication modules
TIM 44 / TIM 44D
Integrated modem MD4
Transmission path
Available standard transmission standards
Approvals
Compatible with SINAUT modems
•
The use of TD7onCPU over backplane bus is possible with the following CPU types:
1)
All variants of the CPU 313C, CPU 314 and CPU 314C;
the CPU 315-2 DP and the CPU 315F-2 DP;
all variants of the C7 devices C7-633, C7-635 and C7-636
The MPI ports of the S7-300-CPU can be used with the following CPU types:
2)
All variants of the CPU 312, CPU 312C, CPU 314 and CPU 314C;
the CPU 315-2 DP and the CPU 315F-2 DP
Technical specifications of the TIM 4V / 4VD
TIM 4V / TIM 4VD
General
Transmission rate
Interfaces
•
•
•
•
Power supply
Current consumption
•
•
Power loss
Permitted ambient conditions
•
•
•
54
LGM64K
Connection to external data transmission
device
MPI bus
DCF77 antenna (TIM 4VD)
Connection to power supply
From backplane bus
From 24 V DC
Operating temperature
Transport/storage temperature
Relative humidity
Digital ISDN network
V.110 1200 bps, duplex
•
V.110 2400 bps, duplex
•
V.110 9600 bps, duplex
•
V.110 19200 bps, duplex
•
X.75 1200 bps, duplex
•
X.75 2400 bps, duplex
•
X.75 19200 bps, duplex
•
X.75 38400 bps, duplex
•
Europe
V.110 9600 bps, duplex
•
50 to 38,400 bps
9-pin D-sub male connector, RS-232 can be
•
switched to RS485
9-pin D-sub female connector
•
BNC socket (over supplied DCF77 adapter
•
cable)
4-pin terminal strip
•
24 V DC; min. 20.4 V; max. 28.8 V
60 mA (only when the TIM is used as a CP in
•
an S7-300 rack)
400 mA
•
9.9 W
0 °C through +60 °C
•
-40 °C through +70 °C
•
Max. 95 % at +25 °C
•
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06