Introduction to the SINAUT ST7 system
2.3 SINAUT TIM communication modules
TIM 44 / TIM 44D
Integrated modem MD4
Transmission path
Available standard transmission standards
Approvals
Compatible with SINAUT modems
The use of TD7onCPU over backplane bus is possible with the following CPU types:
1)
All variants of the CPU 313C, CPU 314 and CPU 314C;
the CPU 315-2 DP and the CPU 315F-2 DP;
all variants of the C7 devices C7-633, C7-635 and C7-636
The MPI ports of the S7-300-CPU can be used with the following CPU types:
2)
All variants of the CPU 312, CPU 312C, CPU 314 and CPU 314C;
the CPU 315-2 DP and the CPU 315F-2 DP
Technical specifications of the TIM 4V / 4VD
TIM 4V / TIM 4VD
General
Transmission rate
Interfaces
Power supply
Current consumption
Power loss
Permitted ambient conditions
54
LGM64K
Connection to external data transmission
device
MPI bus
DCF77 antenna (TIM 4VD)
Connection to power supply
From backplane bus
From 24 V DC
Operating temperature
Transport/storage temperature
Relative humidity
Digital ISDN network
V.110 1200 bps, duplex
V.110 2400 bps, duplex
V.110 9600 bps, duplex
V.110 19200 bps, duplex
X.75 1200 bps, duplex
X.75 2400 bps, duplex
X.75 19200 bps, duplex
X.75 38400 bps, duplex
Europe
V.110 9600 bps, duplex
50 to 38,400 bps
9-pin D-sub male connector, RS-232 can be
switched to RS485
9-pin D-sub female connector
BNC socket (over supplied DCF77 adapter
cable)
4-pin terminal strip
24 V DC; min. 20.4 V; max. 28.8 V
60 mA (only when the TIM is used as a CP in
an S7-300 rack)
400 mA
9.9 W
0 °C through +60 °C
-40 °C through +70 °C
Max. 95 % at +25 °C
SINAUT ST7 Station control system - System Manual
System Manual, 05/2007, C79000-G8976-C178-06